RedLion G315 Load via USB Locks Up Unit

RedLionThe new G315 units (and only the G315s) don’t have USB 2.0 support.  They use USB 1.1.  When you try to load the configuration via USB, it will fail, and it will lockup.

The power-on while holding buttons 1 and 4 trick to reset the IP addresses doesn’t work.

The power-on while holding buttons 1 and 2 to reset the device doesn’t work.

The work-around is to use the ‘file – save image’ option – save file as image.ci3

Write the image file to a Compact Flash card.  Insert in HMI, reboot.

 