RedLion G315 Load via USB Locks Up Unit

RedLionThe new G315 units (and only the G315s) don’t have USB 2.0 support.  They use USB 1.1.  When you try to load the configuration via USB, it will fail, and it will lockup.

The power-on while holding buttons 1 and 4 trick to reset the IP addresses doesn’t work.

The power-on while holding buttons 1 and 2 to reset the device doesn’t work.

The work-around is to use the ‘file – save image’ option – save file as image.ci3

Write the image file to a Compact Flash card.  Insert in HMI, reboot.

 

This entry was posted in Industrial Automation and tagged , , . Bookmark the permalink.

2 Responses to RedLion G315 Load via USB Locks Up Unit

  1. Jon Gooding says:

    Is that really an HMI screen? Looks good but you could not pay me to sit in the control room and stare at something that busy. The color scheme is awful.

Leave a Reply to Jon GoodingCancel reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.